    1. #wiresize_ampacity: "Wire size and ampacity design engineers"
    PowerStream: American Wire Gauge and current capacity
    AWG Wire Sizes (see table below)

    AWG: In the American Wire Gauge (AWG), diameters can be calculated by applying the formula D(AWG)=.005·92((36-AWG)/39) inch. For the 00, 000, 0000 etc. gauges you use -1, -2, -3, which makes more sense mathematically than "double nought." This means that in American wire gage every 6 gauge decrease gives a doubling of the wire diameter, and every 3 gauge decrease doubles the wire cross sectional area. Just like dB in signal levels.


    Metric Wire Gauges (see table below)
    Metric Gauge: In the Metric Gauge scale, the gauge is 10 times the diameter in millimeters, so a 50 gauge metric wire would be 5 mm in diameter. Note that in AWG the diameter goes up as the gauge goes down, but for metric gauges it is the opposite. Probably because of this confusion, most of the time metric sized wire is specified in millimeters rather than metric gauges.

    Load Carrying Capacities (see table below)
    The following chart is a guideline of ampacity or copper wire current carrying capacity following the Handbook of Electronic Tables and Formulas for American Wire Gauge. As you might guess, the rated ampacities are just a rule of thumb. In careful engineering the insulation temperature limit, thickness, thermal conductivity, and air convection and temperature should all be taken into account. The Maximum Amps for Power Transmission uses the 700 circular mils per amp rule, which is very very conservative. The Maximum Amps for Chassis Wiring is also a conservative rating, but is meant for wiring in air, and not in a bundle. For short lengths of wire, such as is used in battery packs you should trade off the resistance and load with size, weight, and flexibility.
    AWG gauge Diameter Inches Diameter mm Ohms per 1000 ft Ohms per km Maximum amps for chassis wiring 在空氣中之單支線 Maximum amps for power transmission 變壓器線圈內 或 兩三線包縛在一起的電纜
    OOOO 0.46 11.684 0.049 0.16072 380 302
    OOO 0.4096 10.40384 0.0618 0.202704 328 239
    OO 0.3648 9.26592 0.0779 0.255512 283 190
    0 0.3249 8.25246 0.0983 0.322424 245 150
    1 0.2893 7.34822 0.1239 0.406392 211 119
    2 0.2576 6.54304 0.1563 0.512664 181 94
    3 0.2294 5.82676 0.197 0.64616 158 75
    4 0.2043 5.18922 0.2485 0.81508 135 60
    5 0.1819 4.62026 0.3133 1.027624 118 47
    6 0.162 4.1148 0.3951 1.295928 101 37
    7 0.1443 3.66522 0.4982 1.634096 89 30
    8 0.1285 3.2639 0.6282 2.060496 73 24
    9 0.1144 2.90576 0.7921 2.598088 64 19
    10 0.1019 2.58826 0.9989 3.276392 55 15
    11 0.0907 2.30378 1.26 4.1328 47 12
    12 0.0808 2.05232 1.588 5.20864 41 9.3
    13 0.072 1.8288 2.003 6.56984 35 7.4
    14 0.0641 1.62814 2.525 8.282 32 5.9
    15 0.0571 1.45034 3.184 10.44352 28 4.7
    16 0.0508 1.29032 4.016 13.17248 22 3.7
    17 0.0453 1.15062 5.064 16.60992 19 2.9
    18 0.0403 1.02362 6.385 20.9428 16 2.3
    19 0.0359 0.91186 8.051 26.40728 14 1.8
    20 0.032 0.8128 10.15 33.292 11 1.5
    21 0.0285 0.7239 12.8 41.984 9 1.2
    22 0.0254 0.64516 16.14 52.9392 7 0.92
    23 0.0226 0.57404 20.36 66.7808 4.7 0.729
    24 0.0201 0.51054 25.67 84.1976 3.5 0.577
    25 0.0179 0.45466 32.37 106.1736 2.7 0.457
    26 0.0159 0.40386 40.81 133.8568 2.2 0.361
    27 0.0142 0.36068 51.47 168.8216 1.7 0.288
    28 0.0126 0.32004 64.9 212.872 1.4 0.226
    29 0.0113 0.28702 81.83 268.4024 1.2 0.182
    30 0.01 0.254 103.2 338.496 0.86 0.142
    31 0.0089 0.22606 130.1 426.728 0.7 0.113
    32 0.008 0.2032 164.1 538.248 0.53 0.091
    Metric 2.0 0.00787 0.200 169.39 555.61 0.51 0.088
    33 0.0071 0.18034 206.9 678.632 0.43 0.072
    Metric 1.8 0.00709 0.180 207.5 680.55 0.43 0.072
    34 0.0063 0.16002 260.9 855.752 0.33 0.056
    Metric 1.6 0.0063 0.16002 260.9 855.752 0.33 0.056
    35 0.0056 0.14224 329 1079.12 0.27 0.044
    Metric 1.4 .00551 .140 339 1114 0.26 0.043
    36 0.005 0.127 414.8 1360 0.21 0.035
    Metric 1.25 .00492 0.125 428.2 1404 0.20 0.034
    37 0.0045 0.1143 523.1 1715 0.17 0.0289
    Metric 1.12 .00441 0.112 533.8 1750 0.163 0.0277
    38 0.004 0.1016 659.6 2163 0.13 0.0228
    Metric 1 .00394 0.1000 670.2 2198 0.126 0.0225
    39 0.0035 0.0889 831.8 2728 0.11 0.0175
    40 0.0031 0.07874 1049 3440 0.09 0.0137
                 
    Voltage Drop Calculator by electrician.com

    The following calculator calculates the voltage drop, and voltage at the end of the wire for American Wire Gauge from 4/0 AWG to 30 AWG, aluminum or copper wire. (Note: It just calculates the voltage drop, consult the above table for rules-of-thumb, or your local or national electrical code or your electrician to decide what is legal!)

    Select Copper or Aluminum

    Select American Wire Gauge (AWG) Size

    Select Voltage

    Enter 1-way circuit
    length in feet

    Enter Load
    in amps


    Voltage drop

    Voltage at load end of circuit

    Per Cent voltage drop

    Wire cross section in circular mils

     

    This chart of American Wire Gauge (AWG) wire sizes and rated ampacities is data intended for the pleasure of our readers only. Typographical errors, etc. are probable, since the typist is not a professional (our CEO). Please point out errors. The data listed are incomplete and should be used as a guideline only. Please contact manufacturers for the latest data.

    We hope that this information is helpful. Now go out and design something that needs a charger, power supply, or battery pack!

    [Home] [PowerStream] [Site Map] [Tech Resources]
      [Policy and Privacy] [Contact Us]

    PowerStream Technology: 140 South Mountainway Drive, Orem Utah 84058
    Phone: 801-764-9060, 9062, 9063 or 9064
    Fax: 801-764-9061

      friends1@powerstream.com

    PowerStream Technology
    140 South Mountainway Dr.
    Orem, UT 84058
    Phone: 801-764-9060, 9062, 9063 or 9064
    Fax: 801-764-9061
    Map & Directions

     

    © Copyright 2000, 2002, 2003, 2004, 2005, 2006 Lund Instrument Engineering, Inc. All rights reserved

    This material is copyrighted original work. It is forbidden to use this information, text, or graphics in full or in part on another web site without written permission.
    AWG Wire current tables. Also electronic wire gauge for current capacities. Gauge load amp wire chart. Wire gauge amp table. Wire gauge to amperage chart. Wire gauge chart. Wire gauge charts. Wire gauge capacity. Guage sizes. Wire gage amp rating. Standard wire gauge table. Wire gauge amperage chart. Current capacity of copper wire. Wire gauge current. Electrical wire size amps. Electric wire size chart. Wire size amperage chart. Wire size awg amps. Wire size current capacity. Wire gage amp rating. Wire size amp rating. Wire size charts. Wire gage amp size. American Wire Gauge

    >2. #AWG_SWG_CSA: http://www.scibore.com/ct/sbuseful.htm
    Sci-bore Wire guide nozzles for manufacture of Coils and Transformers

    Sci-bore 實用資訊
    導線 線規尺寸
    SWG (Standard Wire Guage)
    歐洲使用截面面積 CSA (Cross Sectional Area)
    美國使用美國線規 AWG (American Wire Guage)
    面面積以平方毫米 (mm2) 計算。
    如果某一種類 下面的方框是空的, 這說明該種類沒有相應的產品。
    注意: CSA數值代表相應線規。 如果你遇到1mm的導線, 它可以代替 AWG17 或者 SWG18。
    以CSA尺寸生?的導線 通常有固定的尺寸, 如:0.5 mm, 1.3 mm, 1.5mm等等, 而不是象此處所列的精確尺寸。
    美國 線規 AWG英國 標準線規 SWG實際截面面積 aCSA (mm2)直徑 mm
    500.00050.025
    490.00070.030
    480.00130.041
    470.00200.051
    460.00290.061
    450.00400.071
    400.00490.079
    440.00520.081
    390.00620.089
    430.00660.091
    38420.00820.102
    410.00980.112
    370.01020.114
    400.01170.122
    360.01270.127
    390.01370.132
    350.01580.142
    380.01820.152
    340.02010.160
    370.02340.173
    330.02540.180
    360.02930.193
    320.03200.202
    350.03600.214
    310.04000.226
    340.04300.234
    330.04900.250
    300.05100.255
    320.05700.269
    29310.06500.288
    300.07800.315
    280.08100.321
    290.08600.331
    270.10300.362
    280.12400.397
    260.12800.404
    270.13200.410
    25260.16200.454
    250.19300.496
    240.21000.517
    240.24500.559
    230.25900.574
    230.29500.613
    220.32400.642
    220.41000.723
    210.41200.724
    210.51100.807
    200.55600.841
    190.63600.900
    200.66000.917
    190.81301.017
    180.82601.026
    171.04001.151
    181.17001.221
    161.34001.306
    171.63001.441
    151.68001.463
    14162.08001.627
    132.63001.830
    152.64001.833
    143.25002.034
    114.13002.293
    134.47002.386
    105.26002.588
    125.39002.620
    9116.60002.899
    88.40003.270
    1010.00003.568
    7910.60003.674
    613.00004.068
    516.80004.625
    421.00005.171
    326.20005.776
    233.60006.541